HCS Programmable Temperature Controllers

Programmable Temperature Controllers are microprocessor-based program controllers which store a maximum of 256 segments in 16 patterns (16 segments per pattern). 

Programmable Temperature Controllers are compact 96 mm (4" ) Square DIN size unit that features a unique touch key panel which allows the display section of the front panel to be used not only for setting but also for data entry.

Programmable Temperature Controller Features:

  • Advanced ramp and soak
  • Large memory storage ....16 patterns / 16 segments 
  • Autotuning learning function 
  • Easy programming with unique touch key 
  • Compact size 96 x 96 mm 
  • Audible verification of key operation 
  • Setting lock function for security operation mode 
  • Mode indicators RESET RUN FIX MAN SET enable easy monitoring 
  • Program pattern card simplifies program pattern checking 
  • 3-year warranty

Programmable Temperature Controller Specifications:

INPUT
Thermocouple. . . . Type J, K, T, E, B, R, S, N. (selectable)
RTD. . . . . . . . .PT 100 ohm (DIN or JIS)
Linear. . . . . . . -10-60mV Configurable input other voltage or current.
Display. . . . . . .in temperature or engineering units
OUTPUTS. . . . . . .Single output with 2 optional independent alarms
Heating and / or cooling outputs with 2 optional alarms
Relay. . . . . . . .SPST relay rated 3A, 240V maximum resistive load
Pulsed Voltage. . . 32VDC, 20mA maximum ohms
Current. . . . . . .4-20mA, 0-20mA maximum load 500 ohms
Voltage. . . . . . .0-10V minimum load 500K ohms
Alarms. . . . . . . 8 selectable modes each alarm
SPST relay(s) rated 2A, 240V maximum resistive load.

CONTROL FEATURES
Temp Range. . . . . Selectable Set Point: -1999-3182F / -1128-1750C
Alarm Set Point. . .Full Range Adjustable
Control Modes. . . .Controls can be configured as On/Off Proportional (P)
Proportional with manual reset
Proportional / Integral (PI) Proportional Derivative (PD)
Proportional / Integral / Derivative (PID)
Heating and Cooling Proportional Band:O-100% of span
Integral (Reset). . .0-3600 seconds
Derivative (Rate). . 0-1000 seconds
Anti-Reset Wind-up. Inhibits integral action outside of proportional band.
Cooling. . . . . . .Adjustable deadband from-10 to + 10% of cooling proportional band
Manual Mode. . . . .Configurable as open loop control should sensor no longer function
Cycle Time. . . . . 0-120 seconds
Sensor Break Protection. Configurable status of control and alarms
Control Action. . . Selectable-Direct action for cooling. Reverse action for heating

INDICATION
Display. . . . . . .4 digit red 5/8-in. LED Process Value Display.
Green 1.2-in. LED Set Value display

Selectable decimal placement for normal or high resolution display

Example. . . . . . .0000, 000.0, 00.00 or 0.000
F / C. . . . . . . . .Selectable with 2 LED indicators
Sample Rate. . . . .250 milliseconds
Data Retention. :. .l0 years (EEPROM)
Control Stability. .+ - 0.15% of full scale
Accuracy. . . . . . + -0.25% of range: + ·-1 c or 0.5C in high resolution
Cold Junction Compensation. .0.1% ambient
External Resistance. . . . . 100 ohms maximum
Common Mode Rejection. . . . 120dB
Normal Mode Rejection. . . . 60dB
Input Impedance. . . . . . . 10M ohms
Operating Temperature. . . . 14-122F-10-50C
Humidity. . . . . . . . . . .0-90% RH (non-condensing)
Insulation. . . . . . . . . .20M ohm minimum (500 VDC)
Breakdown. . . . . . . . . . 2OOVAC,50/60Hz 1 minute
Vibration. . . . . . . . . . 10-55Hz amplitude 1 mm
Shock. . . . . . . . . . . . 200m/c (20g)