1/4 DIN Temperature Controllers

FuzyPro 1/4 DIN Temperature Controller Heat/Cool Controllers can easily be configured to provide precise control. Thanks to its advanced Smarter Logic, "Fuzzy" allows processes to be controlled better than ever before, with virtually no initial overshoot or temperature variations. 

As the control detects a process disturbance, the fuzzy logic continuous decision making function quickly returns the process value to the setpoint. The large dual displays allow the set point and process value to be visible at all times. In addition, self-diagnostic capabilities, sensor linearization and cold junction compensation are all performed by the powerful, single chip microprocessor. The 2-in. in-panel depth is the shortest of any similar function control available. 

FuzyPro 1/4 DIN Temperature Controller Heat/Cool Controllers Features:

  • Automatic tuning of PID parameters
  • Selectable input, heating and/or cooling outputs, degrees C or F 
  • 2 optional alarms, large displays 5/8-in. and 1/2-in.
  • Sealed mylar front panel, external lockout 
  • All control parameters adjustable from front panel 
  • Automatic/manual mode operation 2-in. in-panel depth

FuzyPro 1/4 DIN Temperature Controller Heat/Cool Controllers Specifications:

INPUT 
Thermocouple Type J,K,T,E,B,R,S,N. (selectable) 
RTD PT 100 ohm(DIN or JIS) 
Linear -10-60mV Configurable input other voltage or current 
Display  In temperature or engineering units 
Outputs Single output with 2 optional independent alarms
Heating and/or cooling outputs with 2 optional alarms 
Relay SPST relay rated 3A, 240V maximum resistive load 
Pulsed Voltage  32VDC, 20mA maximum ohms
Current 4-20mA, 0-20mA maximum load 500 ohms 
Voltage 0-10V minimum load 500K ohms 
Alarms 8 selectable modes each alarm 
SPST relay(s) rated 2A, 240V maximum resistive load 
CONTROL FEATURES 
Temp Range  Selectable Set Point:
-1999ºF - 3182ºF (-1128ºC - 1750ºC)
Alarm Set Point  Full Range Adjustable
Control Modes Controls can be configured as On/Off Proportional(P)
Proportional with manual reset Proportional/Integral(PI)
Proportional Derivative(PD)
Proportional/Integral/Derivative(PID) Heating and Cooling
Proportional Band:O-100% of span 
Integral (Reset)   0-3600 seconds
Derivative (Rate) 0-1000 seconds 
Anti-Reset Wind-Up Inhibits integral action outside of proportional band 
Cooling Adjustable deadband from -10 to + 10% of cooling proportional band 
Manual Mode  Configurable as open loop control should sensor no longer function
Cycle Time 0 - 120 seconds 
Sensor Break Protection Configurable status of control and alarms 
Control Action Selectable-Direct action for cooling
Reverse action for heating
 
INDICATION
Display  4 digit red 5/8-in. LED Process Value Display. 
Green 1.2-in. LED Set Value display 
Selectable decimal placement for normal or high resolution display
Example  0000, 000.0, 00.00, 0.000
F / C  Selectable with 2 LED indicators
Sample Rate 250 milliseconds 
Power Supply  90-26OVAC, 50/60Hz C;consumption: less than 5VA
Data Retention 10 years (EEPROM) 
Control Stability +/- 0.15% of full scale 
Accuracy -0.25% of range: + -1 c or 0.5C in high resolution 
Cold Junction Compensation 0.1% ambient 
External Resistance 100 ohms maximum 
Common Mode Rejection  120dB
Normal Mode Rejection  60dB
Input Impedance 10M ohms
Operating Temperature  14ºF - 122°F (-10ºC-50°C)
Humidity  0-90% RH (non-condensing)
Insulation 20M ohm minimum (5OOVDC) 
Breakdown 2OOVAC,5O/60Hz 1 minute 
Vibration 10-55Hz amplitude 1 mm
Shock  200m/c(20g)